Yokogawa 414 Batch Controller Manual de usuario Pagina 21

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 59
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 20
Operation 19
3.3 CALCULATION OF RATE AND TOTAL
3.3.1 Frequency Input
The flowrate, R, is calculated as follows:
R = f x H
S
where f is the input frequency in Hz.
H is the timebase of rate and is 1 for seconds, 60 for
minutes, 3600 for hours and 86,400 for days.
S is the Scaling Factor.
The Scaling Factor, S, is equal to the K-factor of the flowmeter expressed in pulses
per unit volume.
The user programs the Scaling Factor and selects the timebase during the
Calibration procedure as detailed in Section 5 of this manual.
Vista de pagina 20
1 2 ... 16 17 18 19 20 21 22 23 24 25 26 ... 58 59

Comentarios a estos manuales

Sin comentarios