<4. Self-diagnostics>
4-3
IM 01C25T03-01E
Indicator BT200 display Cause
Output operation
during error
Countermeasure
AL. 50
P. LRV
50: P ILLEG LRV Specied value is outside of
setting range.
Holds output
immediately before
error occurred.
Check settings and
change them as needed.
AL. 51
P. URV
51: P ILLEG URV
AL. 52
P. SPN
52: P ILLEG SPAN
AL. 53
P. ADJ
53: P SPAN ADJ Continues to operate
and output.
Adjust settings and
change them as needed.
53: P ZERO ADJ
AL. 54
SP. RNG
54: SP ILLEG LRV Continues to operate
and output holding
static pressure in %.
Check settings and
change them as needed.
54: SP ILLEG URV
54: SP ILLEG SPAN
AL. 55
SP. ADJ
55: SP SPAN ADJ Continues to operate
and output.
Adjust settings and
change them as needed.
55: SP ZERO ADJ
AL. 60
SC. CFG
60: SC CONFIG ERR Specied values or settings do
not meet the conditions.
Continues to operate
and output without
signal characterizing.
Check settings and
change them as needed.
AL. 79
OV. DISP
Displayed value exceeds limit. Continues to operate
and output.