<10. EXPLOSION-PROTECTED TYPE INSTRUMENTS>
10-7
IM 01R01B02-00E-E 10th edition January 01, 2013 -00
All Rights Reserved. Copyright © 2003, Rota Yokogawa
Rota Yokogawa
D-79664 Wehr
WT-MAG Mat. No. 16-8040
Serial No, xxxxxxxx
Ex ic IIC T6 Gc
Ui=30V Ii=101mA Pi=1.4W
Li=0.15mH Ci=4.16nF
II 3G
Intrinsic safe power supply for the electronic transmitter :
The power supply for the electronic transmitter may not be installed in the hazardous area, and it may not exceed
the safety relevant maximum values for voltage, current and power of the electronic transmitter as specied above.
Intrinsic safe power supply for the limit switches :
The power supply (transmitter relay) for the limit switches may not be installed in the hazardous area, and it may
not exceed the safety relevant maximum values for voltage, current and power of the connected limit switch as
specied above.
10.4.2 Marking