<2. Handling Cautions>
2-12
IM 01C25B01-01E
Installation Requirements
Uo Ui, Io Ii, Po Pi,
Co Ci + Ccable, Lo Li + Lcable
Voc Vmax, Isc Imax,
Ca Ci + Ccable, La Li + Lcable
Uo, Io, Po, Co, Lo, Voc, Isc, Ca and La are
parameters of barrier.
Note 3. Installation
In any safety barrier used output current
must be limited by a resistor 'R' such that
Io=Uo/R.
The safety barrier must be IECEx certied.
Input voltage of the safety barrier must be
less than 250 Vrms/Vdc.
The instrument modication or parts
replacement by other than authorized
representative of Yokogawa Electric
Corporation and will void IECEx Intrinsically
safe and type n certication.
F0210-1.ai
Pressure Transmitters
IECEx certified
Safety Barrier
Supply
Hazardous Location Nonhazardous Location
General
Purpose
Equipment
+
+
+
+
[Intrinsically Safe]
Group IIC, Zone 0
F0210-2.ai
Pressure Transmitters
Supply
Hazardous Location Nonhazardous Location
+
+
Not Use
Safety Barrier
[type n]
IECEx Certified
Equipment [nL]
Group IIC, Zone 2
b. IECEx Flameproof Type
Caution for IECEx ameproof type.
Note 1. Model EJX/EJA-E Series pressure
transmitters with optional code /SF2 or
/SU2 are applicable for use in hazardous
locations:
No. IECEx CSA 07.0008
Applicable Standard: IEC60079-0:2004,
IEC60079-1:2003
Flameproof for Zone 1, Ex d IIC T6...T4
Enclosure: IP66/IP67
Maximum Process Temperature: 120°C (T4),
100°C (T5), 85°C (T6)
Ambient Temperature: –50 to 75°C (T4),
–50 to 80°C (T5), –50 to 75°C (T6)
Supply Voltage: 42 V dc max.
Output Signal: 4 to 20 mA dc
Note 2. Wiring
In hazardous locations, the cable entry
devices shall be of a certied ameproof
type, suitable for the conditions of use and
correctly installed.
Unused apertures shall be closed with
suitable ameproof certied blanking
elements.
Note 3. Operation
WARNING:
AFTER DE-ENERGIZING, DELAY 5
MINUTES BEFORE OPENING.
WARNING:
WHEN AMBIENT TEMPERATURE 65°C,
USE THE HEAT-RESISTING CABLES
90°C.
Take care not to generate mechanical
sparking when accessing to the instrument
and peripheral devices in a hazardous
location.
Note 4. Maintenance and Repair
The instrument modication or parts
replacement by other than authorized
representative of Yokogawa Electric
Corporation is prohibited and will void IECEx
Certication.
2.10 EMC Conformity Standards
EN61326-1 Class A, Table2 (For use in industrial
locations)
EN61326-2-3
CAUTION
To meet EMC regulations, Yokogawa
recommends that customers run signal wiring
through metal conduits or use shielded twisted-
pair cabling when installing EJX/EJA-E series
transmitters in a plant.