IM 01C22T03-00E
A-1
APPENDIX 1. LIST OF PARAMETERS FOR EACH BLOCK OF THE EJA
APPENDIX 1. LIST OF PARAMETERS
FOR EACH BLOCK OF THE EJA
Note: The Write Mode column indicates the mode in which the parameter is write enabled.
O/S: Write enabled in O/S mode.
MAN: Write enabled in manual mode.
AUTO: Write enabled in auto mode, manual mode, and O/S mode.
--: Read only.
A1.1 Physical Block Parameter List (Slot=0)
Index
16
Parameter
Block Object
Write
Mode
--
Initial Value Description
Information on this block such as Profile, Profile Rev, etc.
18 TAG
AUTO
Specified at the
time of order
The user description of the intended application of the block.
19 Strategy
AUTO
0
The strategy field can be used to identify grouping of blocks.
This data is not checked or processed by the block.
20 Alert key
AUTO
0
The identification number of the plant unit. This information
may be used in the host for sorting alarms, etc.
29 Diagnosis --
Detailed information of the device, bitwise coded. More than
one message possible at once.
30 Diagnosis Extention --
Additional manufacturer-specific information of the device,
bitwise coded.
31 Diagnosis Mask --
Definition of supported DIAGNOSIS information-bits.
0: Not supported
1: Supported
32 Extended Diagnosis Mask --
Definition of supported DIAGNOSIS_EXTENSION information-bits.
0: Not supported
1: Supported
23 Alarm Sum -- For future use.
24 Software Revision -- Uncertain Revision-number of the software of the field device.
25 Hardware Revision -- Uncertain Revision-number of the hardware of the field device.
26 Manufacturer -- Yokogawa Identification code of the manufacturer of the field device.
27 Product designation -- EJA Manufacturer specific identification of the field device.
28 Device Serial Num -- Serial No. Serial number of the field device.
33 Device Certification -- Space Not used for EJA
21
Target Mode AUTO
Auto
Set the Target of block mode to Auto or O/S according to the
Write Mode of the parameter to be set or changed.
22 Mode Block --
The mode parameter is a structured parameter composed of
the actual mode, the normal mode, and the permitted mode.
Actual: Indicates the current operating condition.
Permited: Indicates the operating condition that the block is
allowed to take.
Normal: Indicates the operating condition that the block will
usually take.
17 Static Revision No -- 0
The revision level of the static data associated with the function
block. The revision value will be incremented each time a static
parameter value in the block is changed.
TA 0101-01.EPS