Configuring the GX/GP
1
2
3
4
5
App
Note
If you change the Mode or Range setting, the calibration correction setting is set to Off.
Calibration correction cannot be specified on channels set to Skip or DI.
Explanation
Linearizer Approximation
Corrects input values using characteristics specified with segments to derive output values.
Output value
Measured value
Input value
Number of setpoints: 2 to 12
( )
Linearizer Bias
Corrects input values using bias values specified with segments to derive output values.
Input value
Number of setpoints: 2 to 12
Linearizer bias
After correction
Output value
Measured value
( )
1.2 Configuring AI Channels (Analog input (including DI) channels)