<B4. Power, ground, and signal cable connection>
B4-8
IM 01W02D02-01EN
l Applicable cables
Insulated wires for industrial equipment
Examples:
600 V polyvinyl chloride insulated wires (IV): JIS C3307
Polyvinyl chloride insulated wires for electrical apparatus (KIV): JIS C3316
600 V grade heat-resistant polyvinyl chloride insulated wires (HIV): JIS C3317
Heatproof vinyl insulated wires VW-1 (UL1015/UL1007)
l Wire Size
Core: 2 mm
2
to 2.6 mm
2
(AWG14 to 13)
l Termination
Use a ring tongue terminal for M4 terminals: with an insulation sleeve