4-42
IM WX102-01E
File of Retransmission Output
Set the time constant for abrupt changes in voltage or current being output from the
transmission output module.
Choose a transmission output time constant from the pull down menu. The setting values
and corresponding time constants are as follows:
Value Time Constant (ms) Value Time Constant (ms)
0 4 5 250
1 12 6 500
2 28 7 950
3 60 8 1750
4 125 0 3000
Note
The time constant is for changes from 1 to 5 V, and 4 to 30 mA. If that change is smaller, the
actual time constant will be smaller than the set time constant.
4.19 Setting A/D Converter Integration Time, Filter, and Scan Interval