IM 04L42B01-01E
Taking measures
against noise?
NO
YES
Move the input and communication wires
away from the noise source.
Ground the recorder.
Use shielded cables for input and
communication wires.
Insert an isolation transformer into the
power line.
Insert a power line filter into the power line.
If an inductive load is used in the alarm
output line, insert a serge suppressor in
the line.
Contact your nearest YOKOGAWA
dealer.
Display and other functions do not work properly.
Is the function of the DX
configured properly?
NO
YES
Use the customize-menu function to show
the item on the menu.
Confirm that the DX is equipped with the
necessary options.
Contact your nearest YOKOGAWA
dealer.
Some items on the display selection menu
or FUNC key menu are not displayed.