13-12
IM 04L42B01-01E
Desktop Type (/H5[ ])
Item Specifications
Construction With carrying handle.
/H5D, /H5F, /H5R, /H5J, /H5H: Power Inlet connector. With a power cord.
/H5: Can only be specified when /P1 is simultaneously specified. Screw type power terminal.
Without power cord.
Computation Function (including the report function) (/M1)
Item Specifications
Number of computation channels
DX2004 and DX2008: 12 channels (101 to 112)
DX2010, DX2020, DX2030, DX2040, and DX2048: 60 channels (101 to 160)
Operation
General arithmetic operations:
Four arithmetic operations, square root, absolute, common
logarithm, natural logarithm, exponential, and power
Relational operations:
<,≤,>,≥,=,and≠
Logic operations:
AND, OR, NOT, and XOR
Statistical operations:
TLOG or CLOG
Special operations:
PRE, HOLD, RESET, and CARRY
Conditional operation:
[a?b:c]
Computation accuracy Double-precision floating point
Data that can be used
Channel data Measurement, computation, and external input channels (/MC1)
Constants 60 constants
Communication input data 60
Remote control input status
0/1 (/R1)
Pulse input Counts the number of pulses (/PM1)
Status input Internal switch, alarm output relay (/A[ ]), flags, and recording (memory sampling) status (release
number 3 or later)
Rolling average Performs moving average on the computed results.
Measurement range –9999999 to 99999999
Decimal place: 0 to 4 digits to the right of the decimal point
Alarms High limit, low limit, delay high limit, and delay low limit
Hysteresis: High and low limit alarm: 0.0% to 5.0% of the span.
Display Same as the measurement channels
Data saving Same as the measurement channels
Report function Number of report channels: 12 or 60 (same as the number of computation channels)
Computation types: Average, maximum, minimum, sum, or instantaneous value
Report types: Hourly, daily, hourly + daily, daily + weekly, daily + monthly
Report templates (report output according to templates in XML spreadsheet format; release
numbers 4 and later). Templates (xml files) are available on Excel 2003 or later.
13.5 Options