3-3
IM MV1000-01E
Measurement Channels and Alarms
1
2
3
4
5
6
7
8
9
10
11
12
13
App
Index
3.3 Setting the Input Range
This section explains how to set the input range for each channel.
Display
Press MENU and then select > Menu tab > Meas channel > Range, Alarm.
Settings
First-CH, Last-CH
Select the target channels.
Range > Mode
Setting Description
Skip Not measured.
Volt, TC, RTD, DI, 1-5V Input type. Represents DC voltage, thermocouple, RTD,
ON/OFF input, and 1-5V inputs, respectively.
Delta, Scale, Sqrt Difference computation, linear scaling, and square root
computation.
Select the checked settings for the modes listed below.
Setting Mode
Volt TC RTD DI Delta Scale Sqrt 1-5V Skip
T
ype
Range
Span Lower
Span Upper
Scale Lower
Scale Upper
Un
it
Ref. CH
Low-cut
Low-cut value