3-12
<Toc> <Ind> <3. PC Link Communication >
IM 77J04J11-01E 1st Edition : 2006.08.25-00
BRM Monitors I relays on a bit-by-bit basis
Function
Reads the ON/OFF statuses of the I relays that have been specified in advance by the
BRS command.
Before executing this command, the BRS command must always be executed to
specify which I relays are to be monitored. If no relay has been specified, error code
06 is returned.
For the format of response in the event of failure, see subsection 3.1.2.
The command shown below includes the checksum function.
When performing communication without checksum, do not include the 2-byte
checksum element in the command.
Command/Response (for normal operation)
Number of Bytes 1 2 2 1 3 2 1 1
Command
element
STX 0 BRM ETX CRAddress
number
(ADR)
CPU
number
01
Checksum
Number of Bytes 1 2 2 2 1 1 1 1 2 1 1
Response
element
STX OK d1 d2 d3 ETX CRAddress
number
(ADR)
CPU
number
01
dn Checksum
Responses 0 and 1 indicate OFF and ON respectively.
dn: read data of the number of bits specified by the BRS command (n=1 to 32)
dn=0 (OFF)
dn=1 (ON)
Example:
Monitoring the burnout, alarm 1 and alarm 2 of the M Series with address number 01 when
they have been specified to be monitored.
(This command reads the statuses of the I relays specified by the BRS command.)
[Command]
[STX]01010BRMA3[ETX][CR]
The ON/OFF statuses of the I relays are returned with respect to the above command.
[Response]
[STX]0101OK000EC[ETX][CR]
All have been OFF.