<Toc> <Ind> <6. Functions and Usage of D Registers >
6-3
IM 77J04J11-01E 1st Edition : 2006.08.25-00
6.3.1 Contents of D Registers
D0001: Bit configuration of status
The D0001 register represents errors and parameter data by a combination of bits in the
register.
In the table below, if any of the events shown occurs, the corresponding bit is set to "1."
The bit remains set to "0" if the event has not occurred yet. Note that blank fields indicate
bits not used, which are in "0."
Bit Description
0 Alarm-1 status
1 Alarm-2 status
2
3
4 Input exceeding high limit
5 Input falling below low limit
6 Burnout
7
8
9 EEP sum error
10 Parameter error
11
12
13 RJC error
14 EEP error
15
D0002: Bit configuration of alarm status
Bit Description
0 Alarm-1 status
1 Alarm-2 status
2
3
4 Alarm-3 status
5 Alarm-4 status
6 to 15