Setting group control
After setting display groups, set up group control for the custom display.
Procedure
1.
PresstheMENU key (to Setting mode) and select [Set menu] tab > [Group
tripline] > [Group].
2.
Set the first and last batch group to 1, then enter the group numbers and channel
settings as follows.
Display group setting example
Group No. Group name (leave default) Channels
1 BATCH1-1 001, 002, 003
2 BATCH1-2 004, 005, 006
3 BATCH1-3 007, 008, 009
4 BATCH1-4 010, 011, 012
3.
Return to the custom display builder screen, then press the GR. CTRL soft key.
4.
PresstheGrpCtrl 1 soft key.
The setting screen for GrpCtrl 1 appears.
5.
Enter the following settings.
In the ID boxes, you can only set components for channel assignment (see “ID
Number of Components” in section 1.4).
Group Number
(the group number in step 2)
Order ID
1 1 0, 3, 9
2 1, 4, 10
3 2, 5, 11
Appendix 1 Example of Creating a Custom Display
Vista de pagina 101