Vista de pagina 87
2-58
IM 04L41B01-04E
2.31 Attributes of Communication Input
Components
These components are used to write values to the communication channel. Using the action
function enables numeric values to be written to the specified communication channel on the
execution screen. The value written can be read from other devices using Modbus function.
When you assign the communication channel to the computation channel, you will also be able
to write an arbitrary value to other devices using Modbus function.
Component type
(See Section 1.4.)
Components with
action functions
Overlap restriction
(See Section 1.4.)
None Update
cycle
1 sec
Name of Each Component
The character/value input window shown on the right will
appear when you press DISP/ ENTER after selecting the
communication input components using the up and
down arrow keys on the execution screen.
Communication input value
Background color
Attribute Setting Dialog
List of Attributes
Attribute Description Default value
ID Number automatically assigned for component identification. 0 to 79
Commu data no Sets the communication input data number for entering and
displaying a value.
1
Font Sets the character size. Selectable from [Font 5], [Font 6], [Font
8], [Font 12], [Font 16], and [Font 32].
Font 6(DX1000)
Font 8(DX2000)
Arrangement Sets the horizontal arrangement of the string.Selectable from
[Center], [Left], and [Right].
Right
Color Sets the color of the string. Selectable from among [Red],
[Green], [Blue], [B.violet], [Brown], [Orange], [Y.green],
[Lightblue], [Violet], [Gray], [Lime], [Cyan], [Darkblue], [Yellow],
[Lightgray], [Purple], [Pink], [L.brown], [L.green], [Darkgray],
[Olive], [Darkcyan], [S.green], [Black], [White], and [BASE].
Black
Background color Sets the background color. (Background colors available are
same as those listed in Color.)
White
Decimal place Sets the decimal place of the device that you have connected
using Modbus by the specification of the number of digits to the
right of the decimal point. You can match the decimal place of
the DX to the fixed decimal place of the connected device to
display input values or, using action functions, write values to
the device.
If the input value cannot be displayed using five digits, the sixth
digit is rounded to display five significant digits in scientific
notation.
Range:
[0]
to [4]
Example: If there are two decimal places
Setting value: 2
Displayed value: 123.45
0
Continued on the next page