Yokogawa Standalone MW100 Manual de usuario Pagina 10

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 58
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 9
3. The ―RS Who‖ window will open showing current running drivers. In this example, there is an Ethernet driver
entitled ―AB_ETH-1, Ethernet‖. Click on the ―+‖ symbol to the left of the driver. In the right window, connected
devices are shown.
4. Any devices connected to the ―AB_ETH-1, Ethernet‖ driver now appear in the driver’s tree. In this example, there is a
Compact Logix processor located at IP address 192.168.1.95. For the DX Advanced or MW100 to be used as an
EtherNet IP device communicating to a Rockwell processor, the DX Advanced or MW100 must be mapped to an Ethernet
driver in RSLinx. An existing driver such as the ―AB_ETH-1, Ethernet‖ below may be used or a new driver created. For
this example, we are going to create a new driver in the next step.
7
Vista de pagina 9
1 2 ... 5 6 7 8 9 10 11 12 13 14 15 ... 57 58

Comentarios a estos manuales

Sin comentarios