From the Communication Setting‖ screen,
Select ―Modbus Client Setting 3‖…..
This page is where Modbus addresses are
mapped into Communication Channels for
Reads/Writes to other devices via a ―Command
List‖. For Command ―No. 1‖, select ―Read‖…..
Enter ―1‖ for Server, ―255‖ for Unit, ―18001‖ for
Register. Then Select ―Bit String‖ under ―Data
Type‖. Enter ―C001 for the ―First Channel‖ and
―C005‖ for the ―last Channel‖. Modbus
addresses 18001 thru 18005 are now mapped
to Communication Channels 1 thru 5 which will
now reflect the Status data contained in Modbus
addresses 18001 thru 18005…..
Select ‖Apply‖ when settings
are complete…..