In Rung 0000, a ―MSG‖ instruction reads Math Channel 110 from the DX Advanced and places the value (0 or 1) in word
N7:100. The ―MSG‖ instruction is configured as follows……
Note: SLC 5/05 Data Files start with position 0 (i.e. N7:0). DX Advanced Match Channels start with 101. As a result,
based on the DX Advanced EtherNet IP data mapping tables in chapter 4, there exists an address offset of 1 and the DX
Advanced Math Channel 110 is mapped as N20:9. (N20 for Computation Channel, Integer Value, element #10)