1-4
IM MW100-01E
Main Module
The main module is equipped with power supply connectors, a power switch, Ethernet
ports, and other devices facilitating supply of power to and control of the input/output
modules, and connection to networks.
It also has Start and Stop keys, meaning that since data can be saved to a CF card, data
can be acquired offline. Data acquisition via serial communication is also possible by
adding the RS-232 or RS-422A/485 serial communication option.
Input/Output Modules
The following thirteen types of modules are available. A screw terminal plate and
separately installed screw terminal block (both sold separately) are available as
accessories for the 10-CH, Medium Speed Universal Input Module, the 10-CH, Pulse
Input Module, and the 10-CH, High Speed Digital Input Module.
4-CH, High-Speed Universal Input Module (MX110-UNV-H04)
• Minimum measurement interval: 10 ms
• Maximum number of inputs: 4 inputs
• Input types: DC voltage, TC, 3-wire RTD, and DI (LEVEL,
non-voltage contact)
10-CH, Medium-Speed Universal Input Module (MX110-UNV-M10)
• Minimum measurement interval: 100 ms
• Maximum number of inputs: 10 inputs
• Input types: DC voltage, TC, 3-wire RTD, and DI (LEVEL,
non-voltage contact)