Configuring the DX1000/DX2000
1
2
3
4
5
6
7
8
Index
Serial
For RS-232
• Baud Rate
Select 1200, 2400, 4800, 9600, 19200, or 38400 (bps).
• Parity
Set the parity check method to Odd, Even, or None.
• Data length
Select 7 or 8 (bits). To output the data in binary format, select 8.
• Handshaking
Select Off:Off, XON:XON, XON:RS, or CS:RS.
• Address
For Modbus protocol, enter a value in the range of 1 to 99. For a general purpose
communication protocol, this value is not set.
• Protocol
Select [Normal] for a general purpose communication protocol, [MODBUS] for Modbus
slave, and [Master] for Modbus master.
If Modbus master is selected, Modbus master settings must be entered.
For RS-422/485
• Baudrate
Select 1200, 2400, 4800, 9600, 19200, or 38400 (bps).
• Datalength
Select 7 or 8 (bits). To output the data in binary format, select 8.
• Parity
Set the parity check method to Odd, Even, or None.
• Handshaking
Not specied.
• Address
Select a number from 1 to 99.
• Protocol
This is the same as with the RS-232.
3.6 Entering Basic Settings