1-46
IM 04L21B01-17EN
Writing Measured Values to the Server
Example
Write the measured value (16-bit signed integer) from channel 001 to register 40001
of instrument A.
16-bit signed integer
Measurement channel
Register of instrument A
001 40001
Command setting
W 001 - 001 1 40001 INT16
Writing Computed Values to the Server
Example
Write the computed values (32-bit signed integers) from channel 101 to registers
40001 and 40002 of instrument A, in the order lower 16 bits/higher 16 bits. Only the
smallest register number need be specified in commands.
32-bit signed integer
Computation channel
Register of instrument A
40001
40002
101
lower bytes
higher bytes
Command setting
W-M 101 - 101 1 40001 INT32_L
1.10 Using Modbus to Read Data From and Write Data to Other Devices