2-58
IM 04L21B01-64EN
SNTP Client
Use
Select [Use] to use the SNTP client function; Otherwise, select [Not]. If you select [Use],
the SNTP client settings are displayed.
Server Name
Set the SNTP server name using up to 64 alphanumeric characters.
If the DNS is used, you can set the host name as a server name.
You can also set the IP address. In this case, the DNS is not required.
Port No.
Enter the port number of the SNTP server in the range of 1 to 65535. The default
value is 123.
Access Interval
Set the time interval for synchronizing the time with the server to OFF, 1, 8, 12, or 24h.
If you select OFF, you can synchronize the time manually by operating soft keys. The
time is not synchronized if the difference in the time between the FX and the server is
greater than or equal to 10 minutes.
Ref. Time
Set the reference time for making queries.
Access timeout
Set the time to wait for the response from the SNTP server when querying the time to
10, 30, 90s.
Time adjust (start)
Select [On] to synchronize the time using SNTP when memory start is executed;
Otherwise, select [OFF].
2.6 Entering Basic Settings