Yokogawa Value Series FX1000 Manual de usuario Pagina 75

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 95
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 74
2-62
IM 04L21B01-64EN
Modbus master
Modbus master settings are enabled when you set [Protocol] to [Master] under [Serial] -
[Serial] in the [Basic Setting] tab.
Basic setting
Read cycle
Set the read cycle to 1s, 2s, 5s, or 10s.
Timeout
Set the command timeout value to 125ms, 250ms, 500ms, 1s, 2s, 5s, 10s, or 1min.
Retrials
Set the number of retrials when there is no response from the slave. Select OFF, 1, 2,
3, 4, 5, 10, or 20.
Inter-block delay
Set the inter-block delay to OFF, 5ms, 10ms, 15ms, 45ms, or 100ms.
Auto recovery
Set the auto recovery time from communication halt. Select OFF, 1min, 2min, 5min,
10min, 20min, 30min, or 1h.
Command setting
Command
Set the transmitted command type.
Settings Description
R-Math Read to the communication input channel (32-bit floating point type) from the
slave.
Write Write the measurement channel (16-bit signed integer type) to the slave.
W-Math Write the computation channel (32-bit signed integer type) to the slave.
You can only select [R-Math] or [W-Math] on models that have the /M1, /PM1, or /PWR1 option.
Start channel/End channel (master channel numbers)
Enter the rst and last channel numbers of input/output. The channel numbers that
you can specify vary depending on the command type and are shown below. However,
the total number of channels that you can specify varies depending on the model.
R-Math: C01 to C24, Write: 1 to 12, W-Math: 101 to 124
Address
Enter the address of the slave device in the range of 1 to 247.
2.6 Entering Basic Settings
Vista de pagina 74
1 2 ... 70 71 72 73 74 75 76 77 78 79 80 ... 94 95

Comentarios a estos manuales

Sin comentarios