<4. Installation>
4-1
IM 01C27C01-01EN
4. Installation
4.1 Precautions
Before installing the transmitter, read the cautionary
notes in Section 2.4, “Selecting the Installation
Location. For additional information on the
ambient conditions allowed at the installation
location, refer to Subsection 11.1 “Standard
Specications.”
NOTE
To connect this transmitter to the eld wireless
network, the information on connecting to eld
wireless devices needs to be set beforehand.
Refer to 7.4 “Connecting to the Field Wireless
Network.
IMPORTANT
When welding piping during construction,
take care not to allow welding currents to
ow through the transmitter.
Do not step on this instrument after
installation.
Never loosen the four bolts securing the
cover anges (Refer to gure 3.1.) If the seal
liquid leaks, the transmitter cannot be used.
4.2 Mounting
The transmitter is mounted on a process using its
high-pressure side ange as shown in Figure 4.1.
The mating ange, gasket, stud bolts and nuts are
to be procured by the customer.
Gasket
Stud bolt
Nut
F0401.ai
Figure 4.1 Transmitter Mounting
IMPORTANT
Please use a gasket with an inside diameter
d) that is greater than the diameter of the
diaphragm seal. If a gasket with a smaller
inside diameter is used, the diaphragm may
not function correctly. (Refer to Subsection 11.4
‘Dimensions’)
4.3 Rotating Transmitter Section
WARNING
Intrinsic safe type transmitters must be, as a rule,
do not rotate transmitter section if it is powered.
In case you need to rotate when the transmitter
is powered, using gas detector and conrm no
existence of explosive gas before rotating.
The transmitter section can be rotated in either
direction to any desired position. Note that there is
a stopper which prevents the transmitter from being
rotated more than 360°.
1) Using the Allen wrench, remove the ve
setscrews securing the transmitter section to
the capsule assembly.
2) Rotate the transmitter section slowly to the
desired position.
3) Tighten the ve setscrews to a torque of 1.5
m {15 kgf·cm}.