<8. Setting Parameters>
8-25
IM 01C27C01-01EN
8.4.2 Alert Report
EJX generates alert information related to
Diagnostic Status and automatically sends to a eld
wireless gateway. To use this function, the following
alert setting is necessary. When “Out of Service” for
Diagnostic Status alert is required, choose “FALSE”
for [Out of Service.Alert Disable] in the UAPMO
block. Refer to the eld wireless gateway User’s
Manual for the setting procedure to obtain the alert
information from the gateway.
The alert report consists of the list of parameter
names as shown Table 8.4 below.
Table 8.4 Contents of Alert Report
Parameter name Description
DetectObjectTLPort Alert detection port UAP (0xF0B2)
xed
DetectObject Alert detection block UAPMO (1)
xed
DetectTime Time stamp
AlertDirection 1: generated, 0: clear
AlertPriority Alert priorities set by users
AlertType Alert types, see 8.4 Self-
Diagnostics
AlertValue NAMUR107 category
0:Failure, 1:checkFunction,
2:OffSpec, 3:MaintenaceRequired
CAUTION
For a wireless gateway which does not support
the alert report function, the alert setting in
UAPMO block for the transmitter must be set
to “Disable.” Note that YFGW710 eld wireless
integrated gateway does not have the alert
report function.