<9. Maintenance>
9-2
IM 01C27C01-01EN
Table 9.1 Instruments Required for Calibration
Name Yokogawa-recommended Instrument Remarks
Provisioning
device tool
FieldMate (R2.02.01 or later)
Provisioning Device Tool
Infrared adapter certied by Yokogawa
Supplier: ACTiSYS,Product name: IrDA InfraRed USB Adaptor
Product number: IR224UN
Field wireless
conguration
tool
Field Wireless Integrated Gateway attached Software
Field Wireless Congurator
Field Wireless Management Tool
Field Wireless System related Product
Plant Resource Manager (PRM) (R3.05 or later)
Device Conguration Tool via Wireless Communication
FieldMate(R2.02.01 or later),DeviceFile(R3.01.01 or later)
Device Conguration Tool via Infrared Communication
FieldMate(R2.03.00 or later),DeviceFile(R3.02.01 or later)
Digital
manometer
Model MT220 precision digital manometer
1) For 10 kPa class
Accuracy: ±(0.015% of rdg + 0.015% of F.S.) for 0 to 10 kPa
±(0.2% of rdg + 0.1% of F.S.). . . . . . . . for -10 to 0 kPa
2) For 130 kPa class
Accuracy: ±0.02% of rdg. . . . . . . . . . . . . . . . . . . . for 25 to 130 kPa
±5digits. . . . . . . . . . . . . . . . . . . . . . . . . for 0 to 25 kPa
±(0.2% of rdg + 0.1% of F.S.). . . . . . . . for -80 to 0 kPa
3) For 700 kPa class
Accuracy: ±(0.02% of rdg + 3digits) . . . . . . . . . . . for 100 to 700 kPa
±5 digits . . . . . . . . . . . . . . . . . . . . . . . . for 0 to 100 kPa
±(0.2% of rdg + 0.1% of F.S.). . . . . . . . for -80 to 0 kPa
4) For 3000 kPa class
Accuracy: ±(0.02% of rdg + 10 digits). . . . . . . . . . for 0 to 3000 kPa
±(0.2% of rdg + 0.1% of F.S.). . . . . . . . for -80 to 0 kPa
5) For 130 kPa abs class
Accuracy: ±(0.03% of rdg + 6 digits) . . . . . . . . . . . for 0 to 130 kPa abs
Select a manometer having
a pressure range close to
that of the transmitter.
Pressure
generator
Model MC100 pneumatic pressure standard for 200 kPa {2 kgf/cm
2
}, 25
kPa {2500 mmH2O}
Accuracy: ±0.05% of F.S.
Requires air pressure
supply.
Dead weight gauge tester 25 kPa {2500 mmH2O}
Accuracy: ±0.03% of setting
Select the one having a
pressure range close to that
of the transmitter.
Pressure
source
Model 6919 pressure regulator (pressure pump)
Pressure range: 0 to 133 kPa {1000 mmHg}
Prepare the vacuum pump
for negative pressure
ranges.
Note: The above table contains the instruments capable of performing calibration to the 0.2% level. Since special maintenance and
management procedures involving traceability of each instrument to higher-level standards are required for calibration to the 0.1%
or higher level, there may be difculties in calibration to this level in the eld. For calibration to the 0.1% level, contact Yokogawa
representatives from which the instrument was purchased or the nearest Yokogawa ofce.
F0901.ai
Flange for
calibration
PP
Digital
manometer
Model MC100
Pressure generator
Supply pressure
Pressure source
Reference pressure
Low pressure side
open to atmosphere
(note)
For a diaphragm-extended type, prepare a mating
calibration flange to match the diaphragm extension length
and outer diameter.
(note)
Figure 9.1 Instrument Connections