IM MW100-S16E-1
Ed01
3. Appendix
3.1. DNP device profile
DNP device profile of MW100 special firmware for DNP protocol is shown in Table 69
to Table 71.
Table 69. DNP device profile (1/3)
DNP 3
DEVICE PROFILE DOCUMENT
Vendor Name : Yokogawa Electric Corporation
Device Name : MW100 R3.01 (S16)
Highest DNP Level Supported :
For Request : Level 2
For Response : Level 2
Device Function :
[ x ] Master / Client
[ x ] Slave / Server
Supported Function Blocks :
[ ] Self-Address Reservation
[ ] Object 0 - attribute objects
[ ] Data Sets
[ ] File Transfer
[ ] Virtual Terminal
[ ] Mapping to IEC 61850 Object Models define in a DNP3 XML file
[ ] Function Code 31, activate configuration
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels
Supported (the complete list is described in the attached table) :
Connection Supported :
[ x ] Serial
[ x ] IP Networking
Interval to Request Link Status :
Configurable (none, 1 - 3600 s)
Supports DNP3 Collision Avoidance :
No
Maximum Data Link Frame Size (octets) :
Transmitted : 292
Received : 292
Maximum Application Fragment Size (octets) :
Transmitted : Configurable (200 - 8192)
Received : 8192
Maximum Data Link Re-tries :
Configurable (0 - 5)
Application Layer Re-tries :
None
Requires Data Link Layer Confirmation :
Configurable (never, sometimes, always)
Requires Application Layer Confirmation :
Configurable (never, sometimes, always)