Table 36. Parameters for configuring polling period of DNP master
Kind Configuration
Master
Function
Enabling switch of DNP mater function
- toggle switch to Enable or not
Integrity Poll
Period for polling static data
- configurable within 1 to 3600 [s]
Event Poll
Period for polling event data
- configurable within 1 to 3600 [s]
Response
Timeout
Limit of waiting time for the response corresponding to the command
- configurable within 1 to 60 [s]
- When response is not received over the limit,
DNP master will send the next command.