Table 37. Parameters for configuring polling action of DNP master
Kind Configuration
Address DNP address of the DNP slave
- In case of blank, function is disabled
- configurable within 0 to 65519
Integrity Poll Publishing commands for polling static data
- selectable from “Off”, “Class 0”, “Class 0, 1, 2, 3”
Event Poll Publishing commands for polling event data
- selectable from “Off”, “Class 1, 2, 3”, “Class 0, 1, 2,3”
Unsolicited
Enabling switch for requesting unsolicited message
- selectable from "Enable" or "Disable"