IM MW100-S16E-1
Ed01
Table 40. Parameter for configuring polling action of DNP client
Kind Configuration
Address DNP address of the DNP server
- In case of blank, function is disabled
- configurable within 0 to 65519
Integrity Poll Publishing commands for polling static data
- selectable from “Off”, “Class 0”, “Class 0, 1, 2, 3”
Event Poll Publishing commands for polling event data
- selectable from “Off”, “Class 1, 2, 3”, “Class 0, 1, 2,3”
Unsolicited
Enabling switch for requesting unsolicited message
- selectable from "Enable" or "Disable"
Server IP address of the DNP server
- configurable within 0.0.0.0 to 255.255.255.255
Port Service port of the DNP server
- configurable within 1 to 65535
12
12
Well-known ports for DNP 3.0 protocol are 20000/tcp and udp.