IM MW100-S16E-1
Ed01
Table 22. Parameters for configuring object table
Kind Configuration
Channel Top Top channel of MW100 which show data with DNP objects
- selectable within 001 to 060, A001 to A300 or C001 to C300
Channel Count Channel count of MW100 which show data with DNP objects
- configurable within :
1 to 60 when 001 to 060 is set to top channel,
1 to 300 when 'A' or 'C' channel is set to top channel
Event Class Event class assigned to the DNP objects
- selectable from ”None”, “Class 1”, “Class 2”, “Class 3”
Default Variation Default variation to reply to the request with variation 0
- In case of Binary Input, Binary Output objects, selectable from :
- 1 (Packed Bit)
- 2 (Flag)
- In case of Analog Input objects, selectable from :
- 1 (Int 32 with Flag)
- 2 (Int 16 with Flag)
- 3 (Int 32)
- 4 (Int 16)
- 5 (Short Float with Flag)
- 6 (Long Float with Flag)
- In case of Analog Output objects, selectable from :
- 1 (Int 32 with Flag)
- 2 (Int 16 with Flag)
- 3 (Short Float with Flag)
- 4 (Long Float with Flag)