Table 10. Parameters for configuring polling period and action
Kind Configuration
Integrity Poll Period and publishing commands for polling static data
- period is configurable within 1 to 3600 [s]
- class read :
- selectable from “Off”, “Class 0”, “Class 0, 1, 2, 3”
- command publishing :
- Max. 100 entries
Event Poll Period and publishing commands for polling event data
- period is configurable within 1 to 3600 [s]
- class read
- selectable from “Off”, “Class 1, 2, 3”, “Class 0, 1, 2,3”
Response
Timeout
Limit of waiting time for the response corresponding to the command
- configurable within 1 to 60 [s]
- When response is not received over the limit,
DNP master/client will send the next command.