Table 70. DNP device profile (2/3)
DNP 3
DEVICE PROFILE DOCUMENT
Timeouts while waiting for :
Data Link Confirm : Configurable (1 - 60 s)
Complete Appl. Fragment : None
Application Confirm : Configurable (1 - 60 s)
Complete Appl. Response : Configurable (1 - 60 s)
Unsolicited Confirm : Configurable (1 - 60 s)
Send/Executes Control Operations :
WRITE Binary Outputs : Never
SELECT/OPERATE : Always
DIRECT OPERATE : Always
DIRECT OPERATE-NO ACK : Always
Count > 1 : Never
Pulse On : Never
Pulse Off : Never
Latch On : Always
Latch Off : Always
Queue : Never
Clear Queue : Never
Sequential File Transfer Support :
Append File Mode : No
Custom Status Code Strings : No
Permission Failed : No
File Event Assigned to Class No
File Event Poll Specifically No
Multiple Blocks in a Fragments No
Max Number of Files Open 0
Maximum Time between SELECT and OPERATE :
Configurable (1 - 60)
Supports Unsolicited Reporting :
Configurable
Number of Unsolicited Re-tries :
Configurable (infinite, 0 - 5)
Number of Event Buffer
Configurable (1 - 100)
Hold Time after event
Configurable (0 - 60 s)
Event Reporting Mode :
All Events
Event Buffer Overflow Behavior :
Discard the oldest event
Vista de pagina 125