<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>
9-11
IM 01E30D01-01EN
To release multidrop mode, call up the Poll addr
display and set the address to “0and set the Loop
current mode toEnabled”.
9.8.5 Switching HART Protocol Revision
When the output signal code is “-J”, HART protocol
revision of the device can be selectable from 5 or 7.
The HART protocol revision is set and shipped as
speciedintheorder.
To change the HART protocol revision after
shipment, follow the procedure shown below.
IMPORTANT
Whenchangingtheprotocolrevision,conrmthe
items below.
Protocol revision supported by HART
congurationtoolmustbethesameor
higher than new protocol revision of the
device.
• ConrmthattheDDorDTMwhichissuitable
to new protocol revision of the device is
installedinthecongurationtool.(Referto
Section 9.2)
1) Call up the parameter for protocol revision
change
P
rocedure to call up the Chg universal rev
display.
DD
DTM
[Root Menu]→Detailedsetup→
Deviceinformation→Fielddevice
information→Revision#’s→Chg
universal rev
2) Activate the “Chg universal revmethod
IMPORTANT
The message is displayed to separate the device
from the automatic control loop.
Conrmthatthedeviceisseparated.
3) Input the new revision number
An input column for new protocol revision number is
displayed.
Input the new HART protocol revision number of 5”
for HART 5 or “7” for HART 7.
4
) Applying the new protocol revision
a.Closethecongurationtool
After completion of Chg universal rev
method,closetheHARTcongurationtool.
NOTE
When using a FieldMate, close the main display
of FieldMate.
b. Restart the device
Turn off the power to the device, and turn it
on.
IMPORTANT
New protocol revision is applied only after having
performed restart of the transmitter.
5) Conrmingthenewprotocolrevision
a.RestarttheHARTcongurationtool
NOTE
Whenexecutetheotherparameterconrmation
or setting change, execute after restart the
congurationtool.
b.ConrmthenewHARTprotocolrevision
number
Call up the Universal revparameter,andconrm
that the new HART revision number is displayed.
Procedure to call up the Universal rev.
parameter.
DD
DTM
[Root Menu]→Detailedsetup
→Deviceinformation→Field
deviceinformation→Revision#’s
→Universalrev→
5 HART protocol revision: 5
7 HART protocol revision: 7
HARTprotocolrevisioncanalsobeconrmedon
the second line and third line of the device display.
Procedure to call up the Display Select
DD
DTM
[Root Menu]→DetailedSetup→
FunctionSet→DisplaySet
→Display
Select2 or
Display Select3
Select “Communication”
Protocol Revision DisplayedonAXRscreen
HART Protocol Revision 5 HART5
HART Protocol Revision 7 HART7
9.8.6 Other operations for the HART
congurationtool
Regarding other operations for the HART
congurationtool,refertotheHARTconguration
tool operations manual.