<6. PARAMETER DESCRIPTION>
6-18
IM 01E30D01-01EN
[B30: Total Unit] Setting of units for totalization
scale
→ThissettingislinkedwiththatofparameterD10.
Thisparameterselectstheowrateunitsforusein
totalization.
Item Description
n Unit/P 10
-9
FU
u Unit/P 10
-6
FU
m Unit/P 10
-3
FU
Unit/P FU
k Unit/P 10
3
FU
M Unit/P 10
6
FU
Pulse/s Number of pulses to be counted for one second
at 100% output.
FU: Flow rate unit selected in B21/C40: Base Flow Unit.
[B31: Total Scale] Setting of the totalization scale
→ThissettingislinkedwiththatofparameterD11.
Theowrateistotalizedinindividualcountsin
accordance with this parameter’s setting. If 0 is
selected, it indicates that the totalization function is
not to be used.
NOTE
Ifatotalizationscaleisspecieduponordering,
this parameter is set up before shipment;
however, if this is not the case, it will be
necessary for the appropriate value to be set up
by the user.
NOTE
By setting the totalization scale, the
totalized value is displayed on the display
unit. The totalization scale is determined in
accordance with the settings of B30/D10:
Total Unit andB31/D11:TotalScale.
The maximum value that can be displayed is
99999999, and if this is exceeded, the value
0 is counted once again. However, counting
stops at 99999999 when the totalization
switch function is used.
• Ifmultiplerangesarebeingused,theow
rate span for the smallest range becomes
the standard for the D13: Total Low Cut
setting value.
• Totalizationforthereverseowrateandfor
thedifferentialowrateiscarriedoutonly
when “Fwd/Rev Ranges” is selected for F10:
DO Function.
The totalized units are indicated on the
display unit when B31/D11 is 0.00001,
0.0001, 0.001, 0.01, 0.1, 1, 10, 100, 1000,
or 10000. In the case of other setting values,
the totalized units are not indicated.
Example 1: To count in 1 Ml (mega-liter) steps
withowratespan=1000m
3
/h
Since1Ml=10
3
x m
3
, k Unit/P is set
for B30/D10, and 1 is set for B31/
D11. “x10
3
m
3
is indicated for the
totalized units in the Display Mode.
Example2:Tocountin10l(liter)stepswithow
ratespan=100m
3
/h
Since1l=10
-3
x m
3
, m Unit/P is set
for B30/D10, and 10 is set for B31/
D11. “x10
-2
m
3
is indicated for the
totalized units in the Display Mode.
Example3:Tocountin5l(liter)stepswithow
ratespan=100m
3
/h
Since1l=10
-3
x m
3
, m Unit/P is set
for B30/D10, and 5 is set for B31/
D11. Since B31/D11 is not 0.00001,
0.0001, 0.001, 0.01, 0.1, 1, 10, 100,
1000, or 10000, there is no indication
of totalized units in the Display Mode.
Setting of totalization scale is not possible
whenspecicselectionshavebeenmade
for B
30/D10:TotalUnit,B31/D11:Total
Scale, and B23/C42:FlowSpan. In such
a case, a setting alarm will be displayed,
and parameters should be changed in
accordance with the instructions given.
[B32: Pulse Unit] Setting of the pulse units
This setting is linked with that of parameter E10.
T
hisparameterselectstheowrateunitstobe
used for pulse output.
Item Description
n Unit/P 10
-9
FU
u Unit/P 10
-6
FU
m Unit/P 10
-3
FU
Unit/P FU
k Unit/P 10
3
FU
M Unit/P 10
6
FU
Pulse/s Number of pulses to be output for one second at
100% output.
FU: Flow rate unit selected in B21/C40: Base Flow Unit.