Vista de pagina 139
<10. ACTUAL OPERATION>
10-3
IM 01E30D01-01EN
Sub-item
Parameter
Search Mode
Major item
Sub-item
selection (D)
F1001.EPS
M:Adjustment
21:Adjustment 20mA
10:Auto Zero Exe
11:Autozero Time
Now Auto Zero
Executing
0 100
Auto zero adjustment function is being executed
(about 450 seconds).
When zero adjustment function has been
completed, the system automatically returns to the
sub-item selection screen (D).
NOTE
The results of M10: Auto Zero Exe can
be displayed using M12, M13 and M14.
Alternatively, if the results of the automatic zero
adjustment exceed the rated value, the warning
82: Auto Zero Wng will be displayed.