6-62
IM WX104-01E
Serial
For RS-232
Baud Rate
Select 1200, 2400, 4800, 9600, 19200, or 38400 (bps).
Parity
Set the parity check method to Odd, Even, or None.
Data length
Select 7 or 8 (bits). To output the data in binary format, select 8.
Handshaking
Select Off:Off, XON:XON, XON:RS, or CS:RS.
Address
For Modbus protocol, enter a value in the range of 1 to 99. For a general purpose
communication protocol, this value is not set.
Protocol
Select [Normal] for a general purpose communication protocol, [MODBUS] for Modbus
slave, and [Master] for Modbus master.
If Modbus master is selected, Modbus master settings must be entered.
For RS-422/485
Baud rate
Select 1200, 2400, 4800, 9600, 19200, or 38400 (bps).
Data length
Select 7 or 8 (bits). To output the data in binary format, select 8.
Parity
Set the parity check method to Odd, Even, or None.
Handshaking
Not specied.
Address
Select a number from 1 to 99.
Protocol
This is the same as with the RS-232.
6.5 Entering Basic Settings