6-63
IM WX104-01E
1
2
3
4
5
6
7
8
9
Index
Configuring the DX1000/DX2000
Modbus master
Modbus master settings are enabled when you set [Protocol] to [Master] under [Serial] -
[Serial] in the [Basic Setting] tab.
Basic setting
Read cycle
Set the read cycle to 125ms, 250ms, 500ms, 1s, 2s, 5s, or 10s.
Timeout
Set the command timeout value to 125ms, 250ms, 500ms, 1s, 2s, 5s, 10s, or 1min.
Retrials
Set the number of retrials when there is no response from the slave. Select OFF, 1, 2,
3, 4, 5, 10, or 20.
Inter-block delay
Set the inter-block delay to OFF, 5ms, 10ms, 15ms, 45ms, or 100ms.
Auto recovery
Set the auto recovery time from communication halt. Select OFF, 1min, 2min, 5min,
10min, 20min, 30min, or 1h.
Command setting
Master command No.
Select from 1 to 16 for the command numbers to be congured.
Command
Set the transmitted command type.
Settings Description
Read Read to the external input channel (16-bit signed integer type) from the slave.
R-Math Read to the communication input channel (32-bit floating point type) from the
slave.
Write Write the measurement channel (16-bit signed integer type) to the slave.
W-Math Write the measurement channel (32-bit signed integer type) to the slave.
Exchange-M Read to the communication input data (32-bit floating point type) from the
server/write the custom display value to the server (release numbers 4 and
later).
[Read] can be selected on DX2000s with the external input channel (/
MC1 option) installed.
[R-Math], [W-Mat], and [Exchange-M] can be selected on models with the computation
function (/M1 or /PM1 option) installed.
6.5 Entering Basic Settings