Configuring the CX1000/CX2000
Bias (PV1/2 or Remote)
Turns ON/OFF the use of the bias.
When it is ON, set the value in the EUS (–100 to 100%) range of the measurement.
Filter (PV1/2 or Remote)
Turns ON/OFF the use of the lter.
When it is ON, set the value between 1 and 120 s.
[Linearizer] Tab
Mode
Set the mode to [OFF], [Biasing], or [Approximation].
Input
Set the linearizer input value. (The value varies depending on the mode.)
Biasing: Set the value in EU (–5.0 to 105.0%) of the measurement span.
Approximation: Set the value in EU (–5.0 to 105.0%) of the measurement span.
You must set between 2 and 11 points total.
Output
Set the linearizer output value. (The value varies depending on the mode.)
Biasing: Set the value in EUS (–100.0 to 100.0) of the measurement span.
Approximation: Set the value in EU (–5.0 to 105.0%) of the measurement span.
Note
For biasing, set the values so that input + output is EU (0 to 100%). In addition, set the
values so that input + output is greater than or equal to the previous input + output.
Set the approximation output to be greater than or equal to the previous value.
If a value smaller than the previous value is specified for the third point or later, the settings
after that point are invalid.
When PV/SP math function is OFF, enter the settings above for each control loop in the
[Control Loop] tab. For the setting procedure, see page 6-22.
8.4 Control Function General Settings