8-16
IM WX104-01E
Mode (PV1, PV2, Remote)
Select the channel input mode from [VOLT], [TC], or [RTD]. When [SCALE/1.5V] is set
to [1.5V], [Mode] is set to [VOLT].
Range/Type (PV1, PV2, Remote)
Select the voltage range, thermocouple, and resistive temperature detector type.
VOLT: 20mV, 60mV, 200mV, 2V, 6V, 20V, or 50V
TC: TypeK, TypeJ, TypeT, TypeB, TypeS, TypeR, TypeN, TypeE, TypeL, TypeU,
TypeW, PLATINEL, PR40-20, or WRe3-25
RTD: JPt100 or Pt100
When [SCALE/1.5V] is set to [1.5V], [Range/Type] is set to [6V].
Span (PV1, PV2, Remote)
Specify the measurement span in EU.
Scale (PV1, PV2, Remote)
Specify the scale between –30000 and 30000. However, this is only valid when [SCALE/
1-5V] is set to [Scale]. For details, see the CX User’s Manual (IM 04L31A01-01E or IM
04L31A01-03E).
Unit (PV1, PV2, Remote)
Specify the units.
Use a maximum of 6 characters.
Sqrt (PV1, PV2, Remote)
Select or clear the check box to turn the square root function ON or OFF.
When it is on, set [Low Cut] between 0.0 and 5.0.
Bias (PV1, Remote)
Select the check box to turn the bias ON.
When it is ON, specify a EU (–100 to 100%) value.
Filter (PV1, Remote)
Select the check box to use a filter.
When it is ON, set between 1 and 120.
Ratio setting (Remote)
Turn ON when applying the designated ratio to remote measurement input.
When it is ON, set between –30000 to 30000. Set the decimal point position in the range
of 0 to 4.
On Style 2 or earlier, set between 0.001 to 9.999.
PV Range (PV Range)
Enter the maximum value, minimum value, decimal place, and units.
Set the max. and min. values between –30000 and 30000 such that max. > min., and
max. - min. = 30000.
PV Switching (PV Range)
Set within the input range. When setting Method to T/C Range in the Control Setting
tab within the Setup tab's internal loop item, or when setting Method to PVHigh, only
the upper limit is set. If you set Method to Signal, the PV Input Switching setting is not
available.
8.4 Control Function General Settings